Model |
MS-100-5 |
MS-100-12 |
MS-100-15 |
MS-100-24 |
Output |
DC Voltage |
5V |
12V |
15V |
24V |
Rated Current |
20A |
8.4A |
6.7A |
4.2A |
Current Range |
0~20A |
0~8.4A |
0~6.7A |
0~4.2A |
Rated Power |
100W |
100W |
100W |
100W |
Ripple & Noise (max.) Note.2 |
100mVp-p |
100mVp-p |
120mVp-p |
120mVp-p |
Voltage Adj. Range |
4.75~5.5V |
10.8~13.2V |
13.5~16.5V |
21.6~26.4V |
Voltage Tolerance Note.3 |
±2.0% |
±1.0% |
±1.0% |
±1.0% |
Line Regulation |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
Load Regulation |
±1.0% |
±0.5% |
±0.5% |
±0.5% |
Setup,Rise time |
200ms 100ms |
Hold time (Typ.) |
30ms |
Input |
Voltage Range |
85 ~ 264VAC 120 ~ 370VDC |
Frequency Range |
47~63HZ |
Efficiency(Typ.) |
70% |
76% |
77% |
79% |
AC Current(Typ.) |
0.5A/115VAC 0.25A/230VAC |
Inrush Current (Typ.) |
COLD START 15A/115VAC 30A/230VAC |
Leakage Current |
<0.5mA / 240VAC |
Protection |
Over Load |
105 ~ 150% rated output power |
Protection type : Hiccup mode, recovers automatically after fault condition is removed |
Environment |
Working Temperature |
-10 ~ +60°c (Refer to "Derating Curve" ) |
Working Humidity |
20~90% RH Non-condensing |
Storage temp.& humidity |
-20~+85°C, 10~95%RH |
Temp. coefficient |
±0.03%/°C (0~50°C) |
Vibration |
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes |
Safety & EMC
(Note 4.)
|
Safety Standards |
UL1012, UL60950-1, TUV EN60950-1, CCC GB4943 approved |
Withstand Voltage |
I/P-O/P:1.5KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC |
Isolation Resistance |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC/ 25°c / 70% RH |
EMC Emission |
Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3 |
EMC Immunity |
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, light industry level, criteria A |
Others |
MTBF |
522.1K hrs min. MIL-HDBK-217F (25 °c) |
Dimension |
159*97*37mm (L*W*H) |
Packing |
0.48Kg; 30pcs/4.55Kg/0.9CUFT |
Note |
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25°c of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
|